Thickness Requirements
Roofs
| U-value |
W/m2K |
0.35 |
0.25 |
0.20 |
0.18 |
0.16 |
0.15 |
| ROOFMATE MinK |
| ROOFMATE SL-X |
mm |
80 |
120 |
160 |
180 |
190 |
200 |
| ROOFMATE SL-A |
mm |
100 |
140 |
180 |
200 |
240* |
260* |
| Standard |
| ROOFMATE SL-X |
mm |
100 |
180 |
260* |
300* |
400* |
-- |
| ROOFMATE SL-A |
mm |
120 |
220 |
300* |
360* |
-- |
-- |
Roof build-up:
Ballast (aggregate/pavers)
Separation layer (ROOFMATE MK or geotextile e.g. Terram Roofstat R)
ROOFMATE SL insulation
Separation layer (if required)
Mastic asphalt 30mm
Concrete deck 200mm
*2 layers of insulation required
Floors
| Solid Ground Bearing Floor |
| |
P/A |
0.10 |
0.20 |
0.30 |
0.40 |
0.50 |
0.60 |
0.70 |
0.80 |
0.90 |
1.00 |
| U-values |
|
|
|
|
|
|
|
|
|
|
|
| 0.18 |
|
50 |
70 |
90 |
110 |
110 |
120 |
120 |
140 |
140 |
140 |
| 0.20 |
|
50 |
60 |
80 |
90 |
100 |
110 |
110 |
110 |
120 |
120 |
| 0.22 |
|
-- |
50 |
70 |
80 |
90 |
90 |
100 |
100 |
100 |
110 |
| 0.25 |
|
-- |
50 |
50 |
60 |
70 |
80 |
80 |
80 |
90 |
90 |
| No Insulation |
0.21 |
0.36 |
0.48 |
0.58 |
0.67 |
0.75 |
0.82 |
0.89 |
0.95 |
1.00 |
65mm Screed
| Suspended Beam and Block Floor |
| |
P/A |
0.10 |
0.20 |
0.30 |
0.40 |
0.50 |
0.60 |
0.70 |
0.80 |
0.90 |
1.00 |
| U-values |
|
|
|
|
|
|
|
|
|
|
|
| 0.18 |
|
50 |
90 |
110 |
120 |
120 |
120 |
140 |
140 |
140 |
140 |
| 0.20 |
|
50 |
80 |
90 |
100 |
100 |
110 |
110 |
110 |
110 |
120 |
| 0.22 |
|
50 |
60 |
80 |
90 |
90 |
90 |
100 |
100 |
100 |
100 |
| 0.25 |
|
50 |
50 |
60 |
70 |
80 |
80 |
80 |
80 |
90 |
90 |
| No Insulation |
0.26 |
0.41 |
0.52 |
0.61 |
0.68 |
0.74 |
0.79 |
0.83 |
0.87 |
0.90 |
65mm Screed; block 100 x 440mm, (0.51 W/mK); beam 60mm, (1.13 W/mK)
Agricultural Buildings
| U-values W/m2K |
Roofs |
Walls |
| Heated piggeries1 |
0.5 |
0.5 |
| Unheated piggeries1 |
0.6 |
0.6 |
| Poultry houses2 |
0.4 |
0.4 |
| Crop storage3 |
0.4-0.45 |
0.5 |
1) BS 5502: Part 42
2) MAFF booklet 'Heat Stress in Poultry - solving the problem'
3) BS 5502: Part 71